GB 50116-2013 第3.1.6条 Code for Design of Automatic Fire Alarm Systems

System Equipment消防工程

GB 50116-2013 第3.1.6条

| System bus short-circuit isolator setup: The total number of devices protected by each bus short-circuit isolator, including fire detectors, manual fire alarm call points, and modules, shall not exceed 32 points; when crossing fire compartments, a short-circuit isolator shall be installed in each fire compartment.