ME HotelM&E AI
Home › Standards › GB 51309-2018 › 第3.2.9条

GB 51309-2018 第3.2.9条 Technical Standard for Fire Emergency Lighting and Evacuation Indication Systems

Lighting fixtures电气工程

GB 51309-2018 第3.2.9条

| **** | Evacuation lighting luminaires shall be provided in hotel guest rooms, corridors, stairwells and similar areas. Minimum horizontal illuminance at floor level: evacuation corridors shall not be less than 1.0 lx; densely occupied areas (such as ballrooms and meeting rooms) shall not be less than 3.0 lx; stairwells, antechambers or shared antechambers shall not be less than 5.0 lx. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.