GB 50370-2005 第3.1.6条 Code for Design of Gas Fire Extinguishing Systems

System design消防工程

GB 50370-2005 第3.1.6条

| **** | **Fire resistance and pressure relief**: The fire resistance rating of the enclosure structure, doors and windows in the protected area should not be less than 0.5h, and that of the suspended ceiling should not be less than 0.25h; the allowable pressure of the enclosure structure under internal pressure should not be less than 1200Pa. |