ME HotelM&E AI
Home › Standards › GB 50016-2014 (2018年版) › 第4.4.1条

GB 50016-2014 (2018年版) 第4.4.1条 Code for Fire Protection Design of Buildings

Class A, B, and C liquid and gas storage tanks消防工程

GB 50016-2014 (2018年版) 第4.4.1条

| Fire dike provision for Class A, B and C liquid storage tanks: the effective capacity within the fire dike shall not be less than the capacity of the largest tank in the tank group; the height of the fire dike shall be 1.0 m to 2.2 m and shall be at least 0.2 m above the top of the tank foundation within the dike.

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.