GB 50016-2014 (2018年版) 第4.2.1条 Code for Fire Protection Design of Buildings

Class A, B, and C liquid and gas storage tanks消防工程

GB 50016-2014 (2018年版) 第4.2.1条

| Fire separation distances between Class A, B, and C liquid storage tank farms and buildings: the fire separation distance between Class A and B liquid storage tanks and high-rise civil buildings (including hotels) shall not be less than 50 m, and from podium and multi-storey/single-storey civil buildings shall not be less than 40 m; the fire separation distance between Class C liquid storage tanks and high-rise civil buildings shall not be less than 40 m, and from podium and multi-storey/single-storey civil buildings shall not be less than 35 m.