GB 50084-2017 第7.1.11条 Code for Design of Sprinkler Systems

Sprinkler layout消防工程

GB 50084-2017 第7.1.11条

| | In locations with open-grid ceilings, sprinklers shall be installed below the roof slab. When the open area exceeds 70% of the total ceiling area, sprinklers shall be installed below the roof slab, and the distance from the deflector to the upper surface of the ceiling shall not exceed 100 mm; when the open area does not exceed 70% of the total ceiling area, sprinklers may be installed below the ceiling, and the distance from the deflector to the lower surface of the ceiling shall not exceed 150 mm. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.