GB 50052-2009 第3.6.2条 Code for Design of Power Supply and Distribution Systems

Low-voltage power distribution电气工程

GB 50052-2009 第3.6.2条

| When a single-phase three-wire supply is used, the neutral conductor (N) and the protective conductor (PE) shall be strictly separated, and the neutral conductor current shall not pass through the protective conductor. In hotel buildings, guest room socket circuits shall be provided with residual current protection, with a rated residual operating current not exceeding 30mA.