GB 50052-2009 第3.0.1条 Code for Design of Power Supply and Distribution Systems

Voltage selection and power quality电气工程

GB 50052-2009 第3.0.1条

| The selection of voltage levels for the power distribution system shall be determined based on the capacity of electrical equipment, the power supply distance, and local grid conditions; the low-voltage distribution voltage should preferably be 220/380V. |