GB 7588-2003 第9.2.1条 Safety rules for the construction and installation of elevators

Safety components电梯工程

GB 7588-2003 第9.2.1条

| | **Governor**: The governor tripping speed shall be at least 115% of the elevator rated speed, but shall be less than the following values:<br> - For elevators with rated speed ≤1 m/s: 1.5 m/s;<br> - For elevators with rated speed >1 m/s: 1.25 times the rated speed + 0.25 m/s (and not exceeding 1.5 times the rated speed). |