GB 50736-2012 第8.6.2条 Design Code for Heating, Ventilation and Air Conditioning of Civil Buildings

Monitoring and control暖通空调

GB 50736-2012 第8.6.2条

| The fresh air system should be equipped with a CO₂ concentration detection device and control the fresh air volume accordingly; the fresh air volume control value for hotel guest rooms should be 30 m³/(h·person).