Intelligent Monitoring and Automation Solution for Design Standards

Design Specifications Updated 2026-04-25 0 views

This section introduces the intelligent monitoring and automated control solutions for hotel MEP systems, covering the BAS system architecture, control strategies, and intelligent upgrade pathways.

Building Automation System (BAS) Architecture Design

In accordance with Chapter 18 of GB 51348 and the requirements of GB 50314, the BAS adopts a three-tier network architecture: management tier (central monitoring workstation + servers), control tier (DDC controllers + network controllers), and field tier (sensors + actuators). Management tier configuration: one central monitoring workstation (primary), one backup workstation, one data server (redundant hot standby), and UPS backup of no less than 60 minutes. The software platform adopts BACnet/IP or Modbus TCP open protocols, supporting a scale of 700 points or more. Recommended: Honeywell WEBs-N4, Siemens Desigo CC, Johnson Controls Metasys, or SUPCON iLooP. The control tier establishes network controllers (NCU) by floor or functional zone, each connecting 4–8 DDCs, with 20% spare capacity reserved for total points. A typical hotel has approximately 2,500–4,000 monitoring points. The monitoring scope includes chiller/heater plant systems, air handling terminals, plumbing and drainage systems, power distribution systems, etc. Field devices include temperature sensors (PT100, accuracy ±0.2°C), humidity sensors (accuracy ±2%RH), CO2 sensors (NDIR type, 0–2000 ppm), and motorized control valves (two-way or three-way, 24V/0–10V). The BAS interfaces with fire protection, security, lighting, and guest room systems through standard protocols.

Air Conditioning System Intelligent Control Strategies

Chiller/heater plant group control — automatic staging based on outdoor temperature and return water temperature: when load exceeds 90% of operating capacity and persists for 30 minutes, start an additional unit; when below 35% of total capacity and persists for 30 minutes, stop one unit. Best Efficiency Point (BEP) control — calculate total system power under different combinations based on unit performance curves and automatically select the lowest-energy-consumption combination. Cooling water temperature optimization — calculate setpoint based on outdoor wet-bulb temperature (Ts = WBGT + 3°C) and reset every 15 minutes. AHU/PAU control — supply air temperature PID control at 12–14°C; fresh air damper controlled by CO2 (600–1000 ppm); intermittent operation on holidays. VAV control — room temperature high → damper opens wider → supply airflow increases → fan speeds up. FCU networking — networked to BAS via RS485 or ZigBee for centralized monitoring; guest room FCUs linked via RCU: card inserted → operate per mode; card removed → energy-saving mode after 5 minutes.

Intelligent Lighting and Guest Room Control System Integration

Intelligent lighting adopts DALI or DMX512 protocols. The system architecture includes a central controller, zone controllers (4-channel/8-channel), DALI ballasts, control panels, and sensors. Strategies: lobby automatically switches scenes based on time + illuminance (morning 100%; daytime 80% + curtains open; dusk 60% + wall lights; nighttime 30% + accent lighting). Banquet hall DMX512 dimming with 10 preset scenes for one-touch switching. Corridor occupancy sensing at 10% for energy saving when unoccupied. The RCU guest room control system uses the RCU controller as the core, connecting to electronic door locks (RF card), card-insertion power switches, thermostats (LCD), SOS buttons, infrared sensors, and curtain motors. Linkage logic: card inserted → identification → start air conditioning (24°C in summer, 22°C in winter) → welcome lighting on → open or close curtains. Card removed → 5-minute delay → energy-saving mode (cooling 27°C, heating 18°C) → all lights off → curtains closed.

Energy Management System (EMS) and Data Analytics

The EMS integrates data from BAS, intelligent lighting, RCU, and various sub-metering meters. Data collection: Level 1 metering points (total water inlet, total electricity inlet, total gas inlet) no fewer than 1; Level 2 (by functional zone) no fewer than the number of zones; Level 3 (key equipment) no fewer than the number of equipment units. GB 17167 requires Level 1 coverage of 100%, Level 2 no less than 90%, and Level 3 no less than 70%. Data analytics functions: energy dashboard displaying all metrics in real time, queryable by day/month/year with automatic trend charts. Benchmarking analysis — against historical data (year-on-year, month-on-month), against similar buildings (national average approximately 130 kWh/m²·a; excellent no more than 100), and against design baseline. Anomaly alerts — set operating thresholds; automatic work order triggered when exceeded — e.g., chilled water temperature difference below 3°C (normal 5°C) triggers cooling waste alert; cooling water above 37°C triggers energy efficiency degradation alert; high water usage in guest room areas at night triggers leak alert. Energy consumption forecasting — predict 24-hour load based on historical data and weather forecasts to optimize equipment operation in advance. Carbon management — display carbon footprint data and support carbon emission tracking.