ME HotelM&E AI
Home › Standards › GB 50222-2017 › 第4.0.9条

GB 50222-2017 第4.0.9条 Code for Fire Protection Design of Building Interior Decoration

Fire Protection Facilities and Electrical消防工程

GB 50222-2017 第4.0.9条

| | The illuminance of fire emergency lighting fixtures in buildings shall comply with: the minimum horizontal illuminance on the floor of evacuation walkways shall not be less than 1.0 lx; in densely occupied areas (such as hotel lobbies and restaurants) it shall not be less than 3.0 lx; in stairwells, antechambers or shared antechambers it shall not be less than 5.0 lx. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.