GB 50189-2015 第4.2.16条 Design Standard for Energy Efficiency of Public Buildings

Heating, ventilation and air conditioning暖通空调

GB 50189-2015 第4.2.16条

| **** | In hotel buildings, when an all-air air-conditioning system is adopted, an exhaust air heat recovery device shall be provided, and the rated heat recovery efficiency of the heat recovery device shall not be lower than 60% (sensible heat recovery) or 50% (total heat recovery). |