GB 50189-2015 第4.2.15条 Design standard for energy efficiency of public buildings

Heating, ventilation and air conditioning暖通空调

GB 50189-2015 第4.2.15条

| **** | In large spaces with high occupant density and intermittent use, such as hotel lobbies and restaurants, CO₂ concentration monitoring devices should be installed and linked to control the fresh air volume. When the indoor CO₂ concentration exceeds 1000 ppm, the fresh air volume should be automatically increased. |