GB 50189-2015 第4.2.14条
| **** | Guest rooms in hotels shall be provided with independent temperature control devices, and the air-conditioning system terminals (such as fan coil units) shall have adjustment functions. When a variable air volume (VAV) system is adopted, the minimum supply air volume of the terminal device shall not be less than 30% of the design maximum supply air volume. |