GB 50189-2015 第4.2.5条 Design Standard for Energy Efficiency of Public Buildings

Heating, ventilation and air conditioning暖通空调

GB 50189-2015 第4.2.5条

| **** | When using vapor compression cycle chillers (heat pumps), their Integrated Part Load Value (IPLV) shall not be lower than the provisions of Table 4.2.5. For example: water-cooled screw chillers (cooling capacity >1163kW) IPLV≥7.5; air-cooled scroll chillers (cooling capacity >50kW) IPLV≥4.0. |