GB 50189-2015 第2.0.8条 Design Standard for Energy Efficiency of Public Buildings

Terminology暖通空调

GB 50189-2015 第2.0.8条

| | **Integrated Part Load Value (IPLV)**: An energy efficiency indicator used to evaluate the performance of air-conditioning chillers under part-load conditions. In hotel buildings, when water-cooled chillers are used, their IPLV values must meet the standard requirements (e.g., when the nominal cooling capacity is ≤528 kW, IPLV ≥5.0; when the nominal cooling capacity is >528 kW, IPLV ≥5.5). |