GB 50054-2011 第7.3.2条 Code for Design of Low-Voltage Power Distribution

Laying of distribution lines电气工程

GB 50054-2011 第7.3.2条

| | When insulated conductors are installed exposed indoors, the horizontal run shall be not less than 2.5 m above the floor, and the vertical run not less than 1.8 m above the floor. In hotel guest rooms, exposed conductors should be kept from being lower than 1.8 m (e.g., near the headboard). |