GB 50054-2011 第7.2.11条 Code for Design of Low-Voltage Power Distribution

Laying of power distribution lines电气工程

GB 50054-2011 第7.2.11条

| | When cables are laid in a cable tray, the total cross-sectional area of the cables in the tray shall not exceed 40% of the tray's cross-sectional area; for control cables, it shall not exceed 50%. In hotels, extra-low-voltage cables (such as security and network) and power cables shall be laid in separate compartments. |