ME HotelM&E AI
Home › Standards › GB 50054-2011 › 第4.1.3条

GB 50054-2011 第4.1.3条 Code for Design of Low-Voltage Power Distribution

Layout of power distribution equipment电气工程

GB 50054-2011 第4.1.3条

| **** | **Aisle and operating distance**: The width of the operating aisle in front of switchgear (panels) shall be ≥1.5 m for fixed-type cabinets and ≥1.8 m for drawout-type cabinets; the width of the rear maintenance aisle shall be ≥1.0 m (hotel electrical distribution rooms and LV riser shafts must comply). |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.