GB 50054-2011 第3.1.4条 Code for Design of Low-Voltage Power Distribution

Selection of electrical equipment and conductors电气工程

GB 50054-2011 第3.1.4条

| | The setting current of the **overload protection** device (e.g., circuit breaker) for a distribution line shall be **not greater than** the conductor's permissible continuous current-carrying capacity, and shall be **not less than** the line's calculated current. |