GB 50019-2015 第11.6.1条 Code for design of heating, ventilation and air conditioning of industrial buildings

Monitoring and control暖通空调

GB 50019-2015 第11.6.1条

| The system should have fault alarm functions, including equipment faults (such as fan and water pump overload), parameter out-of-limit conditions (such as chilled water temperature exceeding the set value by ±2℃), filter blockage, etc. In hotel buildings, alarm signals should be transmitted to the central monitoring room or duty room and logged. |