GB 50019-2015 第11.2.1条 Code for Design of Heating, Ventilation and Air Conditioning of Industrial Buildings

Monitoring and Control暖通空调

GB 50019-2015 第11.2.1条

| Monitoring and control of the heating system shall include: supply and return water temperature, pressure, and flow monitoring of the heat source (such as boilers or heat exchange stations); start/stop control and status display of circulating water pumps; room temperature regulation of radiators or underfloor heating systems. The heating system in hotel guest rooms shall be equipped with automatic room temperature control devices, with a control accuracy of ±1℃.