GB 50019-2015 第8.5.2条 Code for Design of Heating, Ventilation and Air Conditioning of Industrial Buildings

Cooling and heating sources暖通空调

GB 50019-2015 第8.5.2条

| | The heating and cooling source equipment room should be located close to the load center and shall meet the requirements for equipment transportation, installation, maintenance and safety clearances. The clear height of the equipment room should not be less than 4.0 m. |