GB 50019-2015 第8.1.3条 Code for Design of Heating, Ventilation and Air Conditioning of Industrial Buildings

Cooling and heating sources暖通空调

GB 50019-2015 第8.1.3条

| | When electric compression chillers (heat pumps) are used, their nominal working condition coefficient of performance (COP) shall not be lower than the provisions of Table 8.1.3. For example: water-cooled chillers (cooling capacity ≤528kW) COP≥4.7; air-cooled chillers (cooling capacity ≤50kW) COP≥2.8. |