GB 50019-2015 第9.5.1条 Code for Design of Heating, Ventilation and Air Conditioning of Industrial Buildings

Air conditioning暖通空调

GB 50019-2015 第9.5.1条

| **** | Air handling equipment in air-conditioning systems (such as air handling units and fan coil units) shall be provided with **air filters**. In densely occupied areas such as hotel guest rooms and restaurants, the initial resistance of the filter should not exceed **50Pa**, and the final resistance should not exceed **100Pa**. |