GB 50019-2015 第9.4.5条 Code for design of heating, ventilation and air conditioning of industrial buildings

Air conditioning暖通空调

GB 50019-2015 第9.4.5条

| **** | The supply-return water temperature difference of the air-conditioning water system should not be less than **5℃** when chillers are used, and should not be less than **10℃** when heat pumps or boilers are used. The hotel air-conditioning system should be equipped with a **differential pressure bypass valve** to adapt to load changes. |