GB 50019-2015 第6.4.1条 Code for Design of Heating, Ventilation and Air Conditioning of Industrial Buildings

Ventilation暖通空调

GB 50019-2015 第6.4.1条

| **** | **Equipment room ventilation**: Independent mechanical ventilation systems should be provided for equipment rooms such as transformer and distribution rooms, diesel generator rooms, and boiler rooms. Generator room air changes: ≥6 times/h under normal conditions, ≥12 times/h under emergency conditions (interlocked with 6.1.5). |