GB 50015-2019 第6.3.1条
| The make-up water volume for the circulating cooling water system shall be calculated at 1%–2% of the circulating water volume, and shall include evaporation, wind drift, and blowdown losses.
| The make-up water volume for the circulating cooling water system shall be calculated at 1%–2% of the circulating water volume, and shall include evaporation, wind drift, and blowdown losses.