GB 50015-2019 第6.2.2条 Standard for Design of Building Water Supply and Drainage

Circulating cooling water给排水

GB 50015-2019 第6.2.2条

| The effective volume of the cooling tower basin shall be calculated as 1.2 to 1.5 times the circulating water flow rate of the cooling tower, and shall not be less than 5 m³.