ME HotelM&E AI
Home › Standards › GB 50015-2019 › 第5.2.16条

GB 50015-2019 第5.2.16条 Standard for Design of Building Water Supply and Drainage

Rainwater给排水

GB 50015-2019 第5.2.16条

| Maximum design drainage flow of rainwater downpipe: DN100 is 19 L/s, DN150 is 38 L/s, DN200 is 75 L/s (based on gravity flow with a fullness ratio of 0.8).

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.