GB 50440-2007 第4.5.2条 Technical Code for Urban Fire Remote Monitoring System

Monitoring center消防工程

GB 50440-2007 第4.5.2条

| **** | The monitoring center shall establish communication links with networked users (hotels) and shall have redundant backup. Reliable communication shall be maintained between the hotel monitoring center and key locations such as floor area displays, the fire pump room, and the power distribution room. |