GB 50440-2007 第4.3.1条
| **** | The monitoring center shall be equipped with an uninterruptible power supply (UPS), whose capacity shall ensure the system can operate normally for no less than 8 hours after the main power supply fails. Since the hotel monitoring center needs to operate 24 hours a day, the UPS capacity shall meet this requirement, and a backup generator is recommended. |