GB 50440-2007 第4.2.1条 Technical Code for Urban Fire Remote Monitoring System

Monitoring center消防工程

GB 50440-2007 第4.2.1条

| **** | The monitoring center shall have the functions of real-time monitoring, recording, querying and statistics of fire alarm information from networked users (i.e., the hotel). The hotel monitoring center shall be able to record alarm and fault history data for at least the most recent 1 month. |