GB 51309-2018 第6.0.7条 Technical Standard for Fire Emergency Lighting and Evacuation Indication Systems

Acceptance电气工程

GB 51309-2018 第6.0.7条

| **** | The continuous emergency operating time of the system shall not be less than 30 min (hotel buildings are classified as places with high occupant density, so a minimum of 90 min is typically required; follow the design documents for the specific value). |