GB 51309-2018 第3.2.7条
| **** | The earthing protection of system circuits shall comply with the requirements of GB 50054 "Code for Design of Low Voltage Power Distribution", and where residual current protection (RCD) is provided, the operating current shall not exceed 30mA, but the system power supply shall not be cut off (alarm only). |