GB 51309-2018 第3.2.7条 Technical Standard for Fire Emergency Lighting and Evacuation Indication Systems

Circuit电气工程

GB 51309-2018 第3.2.7条

| **** | The earthing protection of system circuits shall comply with the requirements of GB 50054 "Code for Design of Low Voltage Power Distribution", and where residual current protection (RCD) is provided, the operating current shall not exceed 30mA, but the system power supply shall not be cut off (alarm only). |