GB 50370-2005 第6.0.4条 Code for Design of Gas Fire Extinguishing Systems

Safety requirements消防工程

GB 50370-2005 第6.0.4条

| | After fire extinguishing, the protected area shall be ventilated and air-changed. For underground protected areas and above-ground protected areas without windows or with fixed window sashes, mechanical exhaust devices shall be provided. The exhaust outlets should preferably be located at the lower part of the protected area and shall lead directly to the outdoors. |