ME HotelM&E AI
Home › Standards › GB 50370-2005 › 第3.1.9条

GB 50370-2005 第3.1.9条 Code for Design of Gas Fire Extinguishing Systems

Pipe network calculation消防工程

GB 50370-2005 第3.1.9条

| **** | **Flow velocity limit**: The flow velocity of the extinguishing agent in the pipe shall not exceed 15 m/s (HFC-227ea) or 10 m/s (IG541), to avoid pipe vibration or noise caused by high-speed flow that could affect the hotel environment. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.