GB 50370-2005 第3.1.7条 Code for Design of Gas Fire Extinguishing Systems

System design消防工程

GB 50370-2005 第3.1.7条

| **** | **Pressure relief opening setup**: The protected area should be equipped with a pressure relief opening, preferably on an exterior wall; for heptafluoropropane and IG541, the pressure relief opening should be located above 2/3 of the clear height of the protected area. |