GB 50370-2005 第3.1.4条 Code for Design of Gas Fire Extinguishing Systems

System design消防工程

GB 50370-2005 第3.1.4条

| **** | **Protected zone division**: A protected zone should preferably be divided as a single enclosed space; when the ceiling plenum and the underfloor space of the same compartment require simultaneous protection, they may be combined into one protected zone. |