GB 50015-2019 第3.2.1条 Standard for Design of Building Water Supply and Drainage

Circulating cooling water给排水

GB 50015-2019 第3.2.1条

| The circulating cooling water system shall be provided with water quality stabilization treatment measures, including scale inhibition, corrosion inhibition, sterilization and algae removal, etc. The cycles of concentration should not be less than 3.0 and should not be greater than 5.0.