GB 50067-2014 第5.1.1条 Code for fire protection design of garage, repair garage and parking lot

Fire compartment消防工程

GB 50067-2014 第5.1.1条

| **** | The maximum permitted floor area of a fire compartment in a garage shall comply with the provisions of Table 5.1.1. For underground garages (including semi-underground), the maximum permitted floor area of a fire compartment is 2000 m²; where an automatic fire-extinguishing system is provided, this may be increased by a factor of 1.0 (i.e., 4000 m²). |