ME HotelM&E AI
Home › Standards › GB 50217-2018 › 第7.0.5条

GB 50217-2018 第7.0.5条 Standard for Cable Design of Electric Power Engineering

Fire prevention and flame retardancy电气工程

GB 50217-2018 第7.0.5条

| **** | The selection of flame-retardant cables shall comply with the following provisions:<br>1. For cables laid in bundles, selection shall be based on the volume of non-metallic materials and the flame-retardant category (Class A, B, C, D);<br>2. For cables laid in bundles within the hotel, the flame-retardant performance shall not be lower than Class C, and for important circuits (such as fire protection and emergency), it shall not be lower than Class B. |

Other clauses of this standard

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.