GB 50217-2018 第5.7.3条 Standard for Design of Cables in Power Engineering

Cable laying电气工程

GB 50217-2018 第5.7.3条

| Where cables penetrate floor slabs, firewalls and partition walls, they shall be tightly sealed with firestop materials. Where cables in the hotel penetrate partition walls between guest rooms and corridors, and floor slabs between equipment floors and guest room floors, the sealing must achieve the same fire resistance rating as the building element (e.g., 1.5 h or 2.0 h).