GB 50217-2018 第3.2.3条 Standard for Design of Cables in Power Engineering

Cable cross-section电气工程

GB 50217-2018 第3.2.3条

| **** | The cable conductor cross-section shall meet the short-circuit thermal stability requirements. Cables from the hotel's transformer and distribution room to fire loads (such as fire pumps and smoke exhaust fans) shall have their thermal stability cross-section verified according to the short-circuit capacity. |