GB 50311-2016 第7.0.5条 Code for Engineering Design of Generic Cabling System

Shielding and grounding弱电智能化

GB 50311-2016 第7.0.5条

| **** | Wiring equipment (such as cabinets and patch panels) in the telecommunications room (weak-current room) shall be reliably grounded. Cabinets shall be connected to the floor grounding terminal board via grounding conductors, and the cross-sectional area of the grounding conductor shall not be less than 6 mm² (copper core). |