GB 50311-2016 第7.0.3条 Code for Engineering Design of Generic Cabling System

Shielding and grounding弱电智能化

GB 50311-2016 第7.0.3条

| **** | Grounding of shielded cabling systems should use single-point grounding. When two or more grounding electrodes exist, the ground potential difference between them should not exceed 1 Vr.m.s. Equipotential grounding terminal boards should be installed in the weak-current (low-voltage) rooms on each floor of the hotel building. |