GB 50015-2019 第6.3.1条 Standard for Design of Building Water Supply and Drainage

Hot water给排水

GB 50015-2019 第6.3.1条

| The hot water supply system shall be provided with circulation piping to ensure that the outlet water temperature at draw-off points is not lower than 45°C; hotel buildings shall adopt mechanical circulation, and the circulation pump flow rate shall be determined according to the head loss of the circulation pipe network.