GB 50242-2002 第8.2.1条 Code for Acceptance of Construction Quality of Building Water Supply, Drainage and Heating Engineering

Indoor domestic hot water给排水

GB 50242-2002 第8.2.1条

| **** | **(Applicable to outdoor heating networks serving hotels)** The hydrostatic test pressure of heating pipes shall be 1.5 times the working pressure, but not less than 0.6 MPa. Under the test pressure, the pressure drop within 10 min shall not exceed 0.05 MPa; then reduce to the working pressure for inspection, with no leakage or seepage. |