GB 50242-2002 第4.5.2条 Code for Acceptance of Construction Quality of Building Water Supply, Drainage and Heating Engineering

Indoor water supply给排水

GB 50242-2002 第4.5.2条

| **** | Hot water supply pipes should use natural bends to compensate for thermal expansion wherever possible; where straight runs are too long, expansion compensators should be installed. The type, specification and location of the compensators should meet the design requirements, and pre-stretching should be carried out in accordance with the relevant provisions. |